■ Connecting with resistance scale, eddy current displacement sensor, etc.
■ 0.2 level accuracy, measuring and controlling speed can be reached at 10 times per second. Display range -1999~9999
■ Panel button and digital input zero function
■ Basic and functional two optional panel styles
■ 8-band polyline correction function
■ Optional can be choosen from 1 to 4 alarm output. Including the upper limit of measurement value, the lower limit of measurement value, the upper limit of deviation, the lower limit of deviation, the absolute value of deviation, five basic alarm modes and five standby alarm modes corresponding to five basic alarm modes
(Standby alarm mode: When the instrument is powered on, it will not alarm even if it is in the alarm area. When the measured value enters the non-alarm area, the standby condition is established, and then the alarm is normal.)
■ 4 optional external power supplies
■ Optional communication, transmission and printing functions.
content | Code description | |||||||||||
XSA- | 0.2 level measurement accuracy; 10 times per second measurement and control speed | |||||||||||
Dimension | AH | 160×80×125 Hole Size:152×76 | ||||||||||
B | 96×96×112 Hole Size:92×92 | |||||||||||
CH | 96×48×112 Hole Size:92×45 | |||||||||||
Panel specifications | 1 | Standard 4 Digit LED | ||||||||||
Signal input | I | DC current(4-20)mA、(0-10)mA、(0-20)mA | ||||||||||
V | DC voltage(0-5)V、(1-5)V | |||||||||||
W | potentiometer(500Ω~10kΩ) | |||||||||||
Contact input (optional) | K | 1 point external switch input for zeroing. | ||||||||||
Alarm | T1~4 | T3、T4 limit AH、AS、B (250V AC/3A,Resistance load) | ||||||||||
Transmitting (optional) (resolution: 1/3000; load capacity: 600Ω) | A1 | Current output(4-20)mA、(0-10)mA、(0-20)mA | ||||||||||
A2 | Voltage output(1-5)V、(0-5)V | |||||||||||
A3 | Voltage output(0-10)V | |||||||||||
External power supply (optional) (No external power supply is required when the input signal is W (potentiometer) | B1 | 24V±5% 50mA below | ||||||||||
B1G | 24V±5% 100mA below | |||||||||||
B2 | 12V±5% 50mA below | |||||||||||
B2G | 12V±5% 100mA below | |||||||||||
Communication (optional) (communication rate: 2400, 4800, 9600, 19200) (Address: 0-99) | S1 | TC ASCII RS232 | ||||||||||
S2 | TC ASCII RS485 | |||||||||||
M1 | Modbus-RTU RS232 | |||||||||||
M2 | Modbus-RTU RS485 | |||||||||||
Print interface (optional) | P | |||||||||||
Power Specifications | V0 | 100-240V AC 50/60 Hz | ||||||||||
V1 | 10-24VAC 50/60Hz;10-24VDC (limit CH) |